Air-Cooled Chiller
(R410A Inverter Series)
A5ACV - 2009
A5ACV 30 CR
A5ACV 55 CR
A5ACV 75 CR
A5ACV 100 CR
A5ACV 135 CR
A5ACV 210 CR
Models:
Vista de página 0
1 2 3 4 5 6 ... 98 99

Resumo do Conteúdo

Página 1 - (R410A Inverter Series)

Air-Cooled Chiller(R410A Inverter Series)A5ACV - 2009A5ACV 30 CRA5ACV 55 CRA5ACV 75 CRA5ACV 100 CRA5ACV 135 CRA5ACV 210 CRModels:

Página 2 - TABLE OF CONTENTS

3. HARDWARE DESCRIPTION Legend 3.1 Key Explanation The 2 navigation keys permit item selection and modifying the selected value. E

Página 3 - 1. NOMENCLATURE

4. INSTALLATION 4.1 Chiller BusChiller NetworkChiller panel needs to be energized with +12Vdc. The 5 way wires that provided is once on the easiest

Página 4 - PRODUCT LINE UP

4.2 Others Configuration • JH2 in chiller panel should let it open (put the jumper header on one pin only) all the time unless user

Página 5 - 2. FEATURES

5. SOFTWARE DESCRIPTION5.1 IntroductionThe Chiller Panel Controller can be used to control / display the status of Chiller.Status viewing:• ON/OFF sta

Página 6 - 3. APPLICATION INFORMATION

5.2 Menu Structures12Status Inverter Chiller Summary Pages Main Menu Unit Selection Menu Operation Menu Settings Menu Timer Menu Alarm Menu Display Me

Página 7

5.3 Chiller Menu Structure5.3.1 Summary PagesThere are 4 pages in [Summary Pages]. Press UP or DOWN for page scrolling. Press ENTER to go to[Main Menu

Página 8 - Refrigerant Circuit Diagram

5.3.2 Main MenuPress ENTER in [Summary Pages] to go into this menuThere are 5 sub menus in [Main Menu]. Press UP or DOWN to select sub menus, ENTER to

Página 9 - 2. GENERAL DESCRIPTION

5.3.2.2 Settings MenuSelect [Settings Menu] in [Main Menu] and press ENTER to go into this menu.Some advance settings can be found here. Press UP or D

Página 10 - 3.1 Key Explanation

5.3.2.2.3 Panel OptionSelect [Panel Option] in [Setting Menu] and Press ENTER to go into this menu.User can do some miscellaneous for the panel. These

Página 11 - Chiller Network

175.3.2.3 Timer MenuSelect [Timer Menu] in [Main Menu] and press ENTER to go into this menu.All the timer/ schedule settings are included in this menu

Página 12

TABLE OF CONTENTS1. NOMENCLATURE ... 1- PRODUCT

Página 13

5.3.2.3.2 Set DateSelect [Date Setting] in [Timer Menu] and press ENTER to go into this menu.User can set the date in this menu. The date is set accor

Página 14 - 5.2 Menu Structures

5.3.2.4.1 Show AlarmsSelect [Show Alarms] in [Alarm Menu] and press ENTER to go into this menu.User can view all the fault/ alarm records in this menu

Página 15

5.3.2.5.1 Defrost SensorSelect [Defrost Sensor] in [Display Menu] and press ENTER to go into this menu.User can view the defrost sensor temperature fo

Página 16

6. OPERATION USER MANUAL6.1 StartingChiller panel can be set as Master or Slave panel unit. When the Panel ID is set to ‘0’, it acts like a Masterpane

Página 17

226.2 CHILLER OPERATION CONTROL6.2.1 STARTINGDuring power on for the Chiller Panel, it needs to take several times to collect information from the Chi

Página 18 - Ple ase enter the

6.2.3 Switching On/OffThere are several ways to switch ON/OFF for the Chiller.i) [Summary Pages] Press and hold ON/OFF button (hold 1 second). Pleas

Página 19

6.2.4 Switching ModeThere are several ways to switch the mode for the Chiller. Please take note that some mode cannot be setdue to current Chiller mod

Página 20

6.2.5 Changing Mode Set TemperatureThere are 2 ways to change the mode set temperature for the Chiller.i) [Operation Menu]25 <ENTER> <ENTE

Página 21

6.2.6 Manual DefrostUser can choose which compressor will go into manual defrost cycle by using the Chiller Panel, as longas the condition is fulfille

Página 22

6.2.7 Advance Parameter SettingsThe Chiller Panel provide user a lot of advance parameter settings for the Chiller. The parameters aredivided into 7

Página 23 - 6. OPERATION USER MANUAL

1. NOMENCLATURE1A AC 100 C R - F X AASeries C : C seriesModel Type R : heatpumpOmitted if coolingCapacity

Página 24 - Cool Temp : 12

3) Compressor4) Condenser Defrost5) Cool Mode Antifreeze6) Inverter7) Alarm and ContactPlease refer to 8. APPENDIX for detail desciption.28C1 Min Run

Página 25

6.2.8 Changing PasswordFor security purpose, some places in the panel are password-proctected. User can change the passwordat anytime.User needs to en

Página 26

6.2.9 Clock SettingUser can set the clock for the panel. Set Time : hh mm 00 : 00 Set Time : yyyy hh mm 2000 /01 / 01 UP or DOWN to change

Página 27

6.2.11 7 Days Programmable SettingThe are 2 ON/OFF events in one day for the schedule. This schedule is applicable to all the chillers inthe network.U

Página 28

6.2.12 Viewing Alarm / Erase Alarm RecordWhenever a new fault/ alarm is occurred, there will be a message pop up to show the fault/ alarm.Backlight wi

Página 29

6.2.13 Viewing Defrost Sensor TemperatureThe Chiller Panel displays defrost sensor temperature for each compressor in [Defrost Sensor]in [Display Menu

Página 30

6.2.15 Viewing / Clear Compressor Run TimeUser can view/ clear the compressor run time for the Chiller in [Comp Run Time] in [Display Menu].Press UP

Página 31 - Change Password

* This product must be branded. Screen saver will be deactivated for brand less panel6.3 CMOS Reset• CMOS reset allows user to reset some settings to

Página 32 - Set Time

Symptoms Possible Cause Troubleshooting1 Panel gets hot - Wiring fault in 12VDC supply - Change a new panel module and turn ON the unit againabnormal

Página 33 - Set Schedule

8. APPENDIX37General Unit Default Min Max ResolutionModel Flag4 0210=Chiller (Chiller+Boiler)1=Heat pump,2=Chiller/ Boiler,3=Heat pump/ Boiler, 4=Chil

Página 34

A5ACV PRODUCT LINE-UP2 PRODUCT LINE UPWired handset WCCHGold FinIsolator SwitchTerminal blockScroll compressorCapillary tube (Normal circuit)Capill

Página 35 - Comp 1 : 12.8°C

COOL MODE ANTIFREEZE Unit Default Min Max ResolutionA1 Antifreeze heater set-point °C (F) 5 (41) -40 (-40) 40 (104) 1A2 Antifreeze heater differential

Página 36

SPECIAL PRECAUTIONS WHEN DEALING WITH REFRIGERANT R410A UNIT1) WHAT IS NEW REFRIGERANT R410A?R410A is a new HFC refrigerant which does not damage the

Página 37 - • Procedures

d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is toensure that only the original composition of R4

Página 38

INSTALLATIONA5ACV 30/ 55/ 75CR41

Página 39 - 8. APPENDIX

A5ACV 30CRA5ACV 55CR / 75CR42

Página 40

A5ACV 100 / 135 / 210CR43SAFETY PRECAUTIONSBefore installing the air conditioner unit, please read the following safety precautions carefullyWarning!

Página 41

CautionPlease take note of the following important points when installing.• Do not install the unit where leakage of flammable gas may occur.If gas l

Página 42

PPPRESSURE GAUGEPRESSURE GAUGEGAGATETEVAVALLVVEEGAGATETEVAVALVLVEEBALANCINGBALANCINGVAVALVLVEETTHERMOMETERHERMOMETERFFLEXIBLELEXIBLEGAGATE VTE VAALLVE

Página 43 - A5ACV 30/ 55/ 75CR

CAUTION ELECTRICAL AND WIRING• Refer to the wiring diagram provided on the unit when making electrical wiring.• Do not ground any electrical equipment

Página 44 - A5ACV 55CR / 75CR

• All terminals and connection must be tightened.• Avoid any wires from touching the refrigerant pipe. Apply insulation if necessary.• Avoid any wires

Página 45

2. FEATURES3TRUE DUAL CIRCUITS BPHEThe true dual BPHE puts the secondary circuit (water) in contact with 2 primary circuits (refrigerant). So eveni

Página 46 - Figure 1

CONTROL OPERATION GUIDEThe unit is equipped with a microprocessor controller board. The microprocessor contorller is provided togive temperature contr

Página 47 - A5ACV 30 / 55 / 75CR

4. SOUND DATA49Sound Pressure LevelOverall125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)A5ACV 30CR5660595348433859A5ACV 55CR6063615652464262A5ACV 75CR

Página 48

5. SELECTION PROCESSWATER PRESSURE DROP VS FLOW RATEMODEL : A5ACV 30CR - COOLINGWater Flow m3/hrPump Head kPaSystem Head kPaAvailable Head Presure

Página 49 - Caution

MODEL : A5ACV 75CR - COOLING / HEATINGWater Flow m3/hrPump Head kPaSystem Head kPaAvailable Head Presure kPa2.20 315.00 21.78 293.222.60 300.00 31.81

Página 50 - CONTROL OPERATION GUIDE

52CORRECTION FACTORS WITH GLYCOL USEWATER PRESSUREFLOW DROP10 1.015 1.0620 1.04 1.1230 1.08 1.1840 1.135 1.24GLYCOL %LWT/ deg C 10 20 30 40-5 0.89 0.8

Página 51 - Sound Power Level

6. ENGINEERING AND PHYSICAL DATA GENERAL DATA - HEAT PUMP R410A INVERTER1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT P

Página 52

GENERAL DATA - HEAT PUMP R410A INVERTER1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING T

Página 53

GENERAL DATA - HEAT PUMP R410A INVERTER1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING

Página 54

GENERAL DATA - HEAT PUMP R410A INVERTER1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING

Página 55

COMPONENTS DATA571) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE

Página 56

3. APPLICATION INFORMATIONREFRIGERANT CIRCUIT DIAGRAMMODEL : A5ACV 30CR4A5ACV 30CRWater / Refrigerant Circuit DiagramPEXVEXVFILFILTERTERDRIERDRIERSU

Página 57

COMPONENTS DATA1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.58A5ACV 100CR A5ACV 135CRmm/in600 / 24 660 / 26I

Página 58

COMPONENTS DATA1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.59A5ACV 210CRPROPELLER2METALDIRECTmm/in812 / 32I

Página 59

SAFETY DEVIES1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.601) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY

Página 60

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.61A5ACV 210CRNCOPEN Pa / psi4140 / 600CLOSE Pa / psi 3312 / 480

Página 61

7. PERFORMANCE DATAMODEL : A5ACV 30CR / 55CR - COOLING62WATER AVAIL. PUMP PUMPCOOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER

Página 62 - SAFETY DEVIES

MODEL : A5ACV75CR - COOLING63WATER AVAIL. PUMP PUMPCOOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT

Página 63

MODEL : A5ACV100 / 135CR - COOLING64WATER AVAIL. PUMP PUMPCOOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD

Página 64 - 7. PERFORMANCE DATA

MODEL : A5ACV 210CR - COOLING65WATER AVAIL. PUMP PUMPCOOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT

Página 65 - MODEL : A5ACV75CR - COOLING

MODEL : A5ACV 30 / 55CR - HEATING66WATER AVAIL. PUMP PUMPHEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT C

Página 66

MODEL : A5ACV 75CR - HEATING67WATER AVAIL. PUMP PUMPHEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRE

Página 67

FIN TUBEHEAT EXCHANGER(SYSTEM 1)FIN TUBEHEAT EXCHANGER(SYSTEM 2)4-WAY VALVEVARIABLE SPEEDCOMPRESSORCOMPRESSORSUCTIONACCUMULATORSUCTIONACCUMULATORWATER

Página 68

MODEL : A5ACV100 / 135CR - HEATING68WATER AVAIL. PUMP PUMPHEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPU

Página 69 - MODEL : A5ACV 75CR - HEATING

MODEL : A5ACV 210CR - HEATING69WATER AVAIL. PUMP PUMPHEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRE

Página 70

8. DIMENSIONAL DATAMODEL : A5ACV 30CR701029,01029,015,015,015,015,080,680,6300,0300,079,479,4406,5406,585,085,070,570,5ELECTRICALELECTRICALCABLECAB

Página 71

MODEL : A5ACV 75CR71741,4741,4205,8205,8205,8205,815,015,0592,4592,415,015,0553,0553,011153,0153,01462,41462,484,084,0210,0210,0244,0244,0AIR VENTAIR

Página 72 - 8. DIMENSIONAL DATA

MODEL : A5ACV100 / 135CR72 All Dimensions are in mm1192.21192.298.798.70.6520.4715.4050.8215.4260.830.071199.21199.21992.51992.550.050.050.050.030.03

Página 73 - MODEL : A5ACV 75CR

9. ELECTRICAL DATA ELECTRICAL DATA - HEAT PUMP R410A INVERTER A5ACV30CR A5ACV55CRF FPOWER SOURCE V/Ph/HzRATED INPUT POWER W135 270RATED RUNNING CUR

Página 74 - All Dimensions are in mm

ELECTRICAL DATA - HEAT PUMP R410A INVERTER1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEI

Página 75 - 9. ELECTRICAL DATA

ELECTRICAL DATA - HEAT PUMP R410A INVERTER751) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE B

Página 76

10. WIRING DIAGRAMS MODEL : A5ACV 30CR76

Página 77

77 MODEL : A5ACV 55CR

Página 78 - 10. WIRING DIAGRAMS

MODEL : A5ACV 210CRFIN TUBEHEAT EXCHANGER(SYSTEM 1)VARIABLE SPEEDCOMPRESSORCOMPRESSORSUCTIONACCUMULATORWATEROUTLIQUIDRECEIVEREXVFILTERDRIERCHECKVALVE

Página 80 - MODEL : A5ACV 75CR

MODEL : A5ACV 100/135CR79zH05/HP3/V514N3L2L1LEP1BT ROTALOSIHCTIWSREDWHITEBLACKBLUENTSRABCGA'B'C'ABCGNA'B'C'N'1RTF)

Página 81 - MODEL : A5ACV 100/135CR

MODEL : A5ACV 210CRROTALOSIHCTIWS1L3L2LNzH05 / HP3 / V514~083RTSNABCGNA’A’B’B’C’C’1RTF)A05(ABCGNA’A’B’B’C’C’N’N’2RTF)A52(2 PMOC1 PMOCPMUPUVWUVWUVW5BT

Página 82

12. SERVICING AND MAINTENANCESERVICINGServicing or maintenance of these unit must be carried out by experienced personnel with specifictraining in r

Página 83 - 12. SERVICING AND MAINTENANCE

13. TROUBLESHOOTING82When a malfunction of the unit is detected, immediately switch off the main power supply before proceedingwith the following tr

Página 84 - 13. TROUBLESHOOTING

Diagnostic flow chart Yes : Faulty : Check : Cause : Remedy No response after power-on Input conditions faulty Is LED main board lit? To check &

Página 85 - Diagnostic flow chart

No LED on main board normal, but no output. Incorrect output condition Is output condition ok? To check & rectify Yes Is load ok? Incorrect load.

Página 86

No Water flow error Flow switch faulty or pump stopped Is water flow error persists? To check & rectify Main board faulty Yes To replace Main boa

Página 87

No Under voltage protection (OV/UN Voltage) Power supply failure Is Power supply > 340VAC? To rectify Power board faulty Yes To replace Power boa

Página 88

Variable compressor overload (Comp 1 overload) Compressor current & circuit is ok Main board/compressor faulty No To check & replace Restart,

Página 89

CHILLER PANEL CONTROLLER1. SAFETY CONSIDERATIONOnly specially trained and technicians and installers are authorized to install and service thisequipm

Página 90

88Is heat sink temperature >100°C? No IPM Error IPM faulty Is IPM ok? To replace IPM Yes Is current at rated frequency ok? Compressor faulty Is I

Página 91

89No Variable drive low pressure (Low pressure 1) Low pressure switch faulty Check the Air-Cond. system for low pressure To replace System low pressur

Página 92

Yes Variable compressor high discharge temperature (Comp 1 discharge overheat) Compressor stops > 110°C? To check & rectify Yes Is Temp. senso

Página 93 - MODEL : A5ACV 30CR

13. EXPLODED VIEW AND PART LISTSMODEL : A5ACV 30CR91No Description Part no No Description Part no 1 ASSY, BASE PAN R50 01 4 079444 19 COMP

Página 94 - MODEL : A5ACV 55CR

92MODEL : A5ACV 55CRNo Description Part no No Description Part no 1 ASSY, PANEL BASE R50 01 4 079682 25 ASSY, TERMINAL BOX MAIN R50 04 4 0820

Página 95

93MODEL : A5ACV 75CRNo Description Part no No Description Part no 1 ASSY, BASE PAN R50 01 4 078737 27 STRUCTURE REAR RIGHT R01 01 4 078641

Página 96 - MODEL : A5ACV100CR

MODEL : A5ACV100CR94NO DESCRIPTIONS PART NO NO DESCRIPTIONS PART NO 1 ASSY, PANEL BASE MAIN R50 01 4 077857 27 PANEL, ORIFICE LEFT R01 01 4 082

Página 97 - MODEL : A5ACV135CR

MODEL : A5ACV135CR95NO DESCRIPTIONS PART NO NO DESCRIPTIONS PART NO 1 ASSY, PANEL BASE MAIN R50 01 4 079125 28 PANEL, RIGHT ORIFICE R01 01 4 0

Página 98 - MODEL : A5ACV210CR

MODEL : A5ACV210CR96NO DESCRIPTION PART NO NO DESCRIPTION PART NO 1 ASSY, PANEL BASE MAIN R50 01 4 084901 30 ASSY, CONTROL BOX R50 04 4 089239

Página 99

While upmost care is taken in ensuring that all details in the publication are correct at time of going to press, we are constantly striving for impro